Latest articles
Troubleshooting
LatestMP377 frozen startup screen: recovery after an interrupted transfer
When power drops during an MP377 project transfer, storage can end up incomplete and the panel hangs at the startup screen without loading its network or transfer services, so ping, ProSave and WinCC flexible all fail. The documented recovery is an operating system update with Reset to factory settings over the panel's recovery connection; a failed ping does not prove the loader is dead, and no project download will land until the OS is rewritten.
Explainer
Why WinCC Professional cannot program a Unified Comfort Panel
A Unified Comfort Panel is programmed only with WinCC Unified Engineering; WinCC Professional builds applications for a different set of targets and cannot download to this panel. Multitouch is a panel capability, not a compatibility path. Before V19 the two engineering packages could not share one PC; from V19 parallel installation is documented.
Explainer
Why an HMI panel runs its own project beside a LOGO 8
A LOGO 8 program never moves to the panel: it is downloaded to the LOGO and runs there. The HMI panel needs its own engineering software, such as WinCC in TIA Portal, and its own visualization project that exchanges data with the controller over an Ethernet connection. Engineer and download the two projects separately, then point the panel connection at the LOGO's IP address.
Explainer
Why an oversized HMI screen cannot show a scroll bar
A panel runtime draws one fixed screen area at the target's native resolution and provides no scroll bar to pan an oversized layout. Redesign the screen for the installed panel: remove or resize objects, split content across screens with arrow navigation, or move detail into popup screens. When the approved layout must stay as drawn, move it to hardware that matches its size.
Troubleshooting
Why an Edge App Fails to Install on a Unified Comfort Panel
An Edge app fails to install on a Unified Comfort Panel because one of three separate limits is exceeded: free storage for the package plus unpacking, total panel RAM shared with everything else, or the 768 MB cap on data memory across all installed apps. Compare each limit against the panel's own readings.
Troubleshooting
Why a Unified Comfort Panel web client shows scrollbars
On V17 Update 7 the panel-integrated web client has no fit-to-window setting, so a screen configured for the panel's native resolution overflows any smaller browser viewport. From V18 Update 1 you set size-fit on the Main screen window. Staying on V17, run the browser fullscreen or fit the layout from a UI.GetClientInfo script.
Troubleshooting
TP1500 Comfort V2 INOX missing from TIA Portal catalog
There is no separate catalog entry or HSP for the TP1500 Comfort V2 INOX: configure the standard TP1500 Comfort V2, order number 6AV2124-0QC02-0AX1, update TIA Portal V16 past its shipping baseline, and install the separately delivered WinCC images. After those three steps the download succeeds against firmware 16.0.0.3.
Troubleshooting
Why the browser shows the IIS page instead of your HMI runtime
A bare hostname makes the browser request HTTP, and the IIS web server on the runtime PC answers with its own default page; the WinCC Unified PC runtime serves browsers only over HTTPS. Type the scheme explicitly — https://localhost on the runtime PC, or https:// followed by the computer name from any workstation — and expect a certificate warning on the first connect.
Explainer
Running a LOGO! Web Editor project beside a TP700 panel
Yes, a LOGO! 8.2 can serve LOGO! Web Editor pages and talk to a TP700 Comfort panel at the same time: the controller has one Ethernet port, so the panel, the controller and the browser PCs all sit on one Ethernet switch; you need LSC V8.2 to build the pages, web server access enabled on the controller, and the pages loaded as one web project.
Troubleshooting
Connect a Comfort Panel to a PLCSIM S7-300 with NetToPLCSim
Classic PLCSIM listens only inside the PC, so a physical TP900 Comfort panel cannot reach it over the network on its own. Run NetToPLCSim with administrative rights before any Siemens software starts, set Network IP Address to the panel-facing adapter, set PLCSIM IP address to the simulated CPU, point the panel's controller connection at the PC adapter address, and keep the S7DOS Help Service off TCP port 102.
Troubleshooting
Why a ProSave Backup Cannot Migrate a Panel PC ProTool Project
No. ProSave backs up and restores panel targets only, and no PC or Panel PC appears in its device list, so a Panel PC 677B backup is not something ProSave produces or that any migration tool can import. The ProTool to TIA Portal route needs the editable ProTool configuration project and runs through WinCC flexible 2008 SP3 or SP5; with runtime only, reinstall ProTool runtime on a compatible 32-bit Windows PC or virtual machine.
Explainer
Why WinCC Flexible 2007 Cannot Open a 2008 Project
WinCC flexible is forward-only: a project saved in 2008 will not open in the 2007 tool, and no service pack or file trick changes that. The documented fix is Save As Version in WinCC flexible 2008, which writes a 2007-format Project.hmi with its Project_log.LDF; on Windows XP Professional SP3, installing 2008 is documented and removes the problem entirely.