IMDTouch field guide
The operator interface.
Select, install and troubleshoot a touch display at the machine. Read the field notes or compare an industrial monitor for your existing PC.
Read the field notes →Touchscreen selection →
IMD / PRODUCT FILMS
Hardware, in its element.
The operator interface. Installed.
A closer look at the panel, the control cabinet, and the interface your operators use.
Rendered IMD product demonstrations.

Touchscreen selection
Compare touch and brightness options for a display connected to an existing PC.
Q-Series 15.6-inch industrial touch monitor
Hardware for HMI and touch projects
Panel PCs, touchscreen monitors, fanless mini PCs and stainless enclosures, configured to the job at Industrial Monitor Direct.
Latest articles
Explainer
LatestWhy KTP400 Basic panels use Time Shift instead of a timezone
A KTP400 Basic panel has no timezone setting; the Control Panel's Date & Time dialog offers a Time Shift field as a signed hour-and-minute value spanning -24:00 to +24:00. Entering +07:00 shifts the panel clock, so a Date/Time field in system-clock mode reads seven hours ahead. Comfort panels get a true timezone setting instead; the procedures are not interchangeable.

Troubleshooting
Why an OPC DA client fails on a third-party OPC server
The question-mark quality is a COM activation failure, not a bad ItemID: when every other OPC client on the same PC reads the tag, the syntax is proven and the WinCC OPC DA client is being denied activation of the server. From WinCC V7.3 on, run Simatic Security Control, grant the local SIMATIC HMI group launch, activation and access rights on the server's COM application, allow the CCDmRtChannelHost callback through the firewall, and restart the computer.
Troubleshooting
Why a Sm@rt Access client view stays small after migration
The Sm@rtClient view scales only in proportion, so a 4:3 remote image on a 16:9 panel always leaves an empty strip: fitted by height, it covers 75 percent of the width. Enlarge the view object and set its own scaling property, because the local Fit to screen choice does not govern the remote view. After that, accept the strip or rebuild the remote project at 16:9.

How-to
WinCC library push button latches: how to get press and release
The library push-button switch is a maintained toggle: it exposes Switch on, Switch off, Activate and Deactivate, and no Press or Release, so a bit set on one click stays set until the next click. Use a normal toolbox Button with SetBit on Press and ResetBit on Release, and reuse the library artwork by setting its Mode to Graphic.

Troubleshooting
Why WinCC flexible 2008 PC Runtime will not reach a VIPA PLC
Choosing Ethernet in the WinCC flexible 2008 project does not bind the Runtime computer's communication software to the right network adapter. Open Set PG/PC Interface in that computer's Control Panel and bind the access point the connection uses to the adapter cabled to the PLC. Then run a STEP 7 upload at the PLC's configured address: if it fails the fault is below the HMI, if it works the fault is in the HMI connection.

Explainer
Why WinCC Flexible 3D pipes scale instead of stretching
Library 3D pipes in WinCC flexible 2005 are single WMF graphics: dragging a handle scales the whole symbol, and no rotate command exists for them. To lengthen an angled run, overlap two or more copies end to end, or export the artwork, rework it outside the tool and import it as a JPG. Read the Hotfix 7 readme before assuming the hotfix changes either limit.

How-to
Running WinCC Runtime Professional V13 on an EC31-RTX IPC
Yes: install only the WinCC Runtime Professional component on the EC31-RTX, leave its preinstalled WinLC RTX V4.6 (WinAC RTX 2010) controller untouched, and keep TIA Portal V13 with STEP 7 and WinCC Professional as the only engineering software. Buy a separate runtime license sized in Power Tags, and gate the install on the operating system: the delivered Windows Embedded Standard 2009 image is XP-class while the V13 runtime is released for Windows 7-class and newer systems, so the delivered EC31 hosts the operator interface elsewhere.

How-to
Connecting a WinCC flexible 2005 Tag to STEP 7 PLCSIM
The order you used is correct: STEP 7 5.3 first, WinCC flexible 2005 second, and SP3 for STEP 7 5.3 last, so no reinstall is needed. Define MD 4 as an external tag on the connection to the simulated controller, marker memory, byte offset 4, 4-byte integer, then force a value in PLCSIM and confirm the HMI follows it.

Explainer
Why WinCC joins SINUMERIK Operate instead of replacing it
WinCC Runtime Advanced does not replace SINUMERIK Operate on a PCU-based 840D sl. It is integrated into Operate and opened from a configured softkey, so the standard screens stay available while you build the machine-specific screens in WinCC. The option required is 6FC5800-0AP61-0YB0 once per NCU; the SIMATIC-panel option in the proposal belongs to a different architecture.
Explainer
Why numeric message codes do not map to discrete alarm bits
The old panel's byte is a numeric selector: the full value picks one text-list entry, and bit 0 has the value 1, so a set trigger bit 0 shows the entry stored under value 1. Keep the value-driven text list for indication; decode each message code into its own discrete alarm condition when you need acknowledgment and alarm history.

How-to
Setting a PLC bit when a WinCC flexible screen is left
On a WinCC flexible 2008 panel, set a bit like stop1200 when the operator leaves a screen by assigning the screen's departure event a bit-setting system function on the connected Boolean tag. No script is needed. Hold the request until the PLC acknowledges it, and handle shutdown, communication loss and power loss in controller logic, never in the departing screen.

Troubleshooting
Why WinCC DataMonitor Viewer RT reports unknown user or bad password
When WinCC DataMonitor Viewer RT reports an unknown WinCC user or bad password, the credentials are usually fine. In a documented V7.2 case the cause was a missing start picture in the WinCC user's Web Options. Set the correct Basic Process Control web start picture, the MainControl.asp default page and the right group memberships.